Danfoss AK-SM 800A Flaws: Attackers Are Using the Old Ones, Not the New One With No Fix
A company that runs supermarket fridges has a choice this week. A new flaw in its fridge controllers has no fix yet. Earlier software versions fixed three older flaws. Which should it deal with first?
- Who should care: Food retailers, and anyone whose buildings run on equipment a contractor installed and manages.
- What could go wrong: Attackers could switch off store refrigeration from afar. BleepingComputer reports this happened in Europe this autumn.
- Do this: Find out which software version each controller is running, and update the old ones now.
- Worth remembering: The flaw in the headlines isn’t always the one you’re using. Check what is installed before you wait for the new fix.
What Happened?
On Friday, November 20, Danfoss disclosed a new flaw in its AK-SM 800A controllers that needs no login. There is no fix yet. Danfoss says version 5.5.x will fix it but gives no date, and CISA’s advisory of November 24 says no attacks using it have been reported to CISA. On November 25, CISA added three older flaws in the same controllers to its list of flaws known to be used in attacks.
Old and Fixable vs. New and Unfixed
Danfoss named the fix for two of the older flaws on August 21, 2023. Danfoss published the record for the third on May 8, 2025. So CISA can fix every flaw it confirms as used today. The new one can’t, and Danfoss says it could only “hypothetically” let an attacker run code.

Do the two 2023 flaws need a login? The public CVE records say yes. Danfoss’s 2023 notice doesn’t say. With the sources split, we won’t guess how easy they are to use.
BleepingComputer reports attackers turned off refrigeration in French stores in October and in six more countries in November. No source says which flaw those attacks used.
What’s the Impact?
A fridge that warms up overnight means stock in the bin. Refrigeration contractors often install and run these controllers, so nobody inside the company may know their software version. CISA gave federal agencies until November 28 to deal with two of the three flaws.
How to Avoid This
- List every AK-SM 800A controller you run, including ones a contractor manages.
- Read the software version each one is actually running.
- Update anything before version 4.2 now. That covers all three flaws on CISA’s list.
- Keep every unit off the public internet and reach it only through a VPN.
- Turn on Strict mode, and assign each controller a named owner within the company.
The Details
| CVE | Fixed in | On CISA’s list | EPSS on November 25, 2026 |
|---|---|---|---|
| CVE-2023-25914 | Version 3.3 | Yes | 1.08% |
| CVE-2023-25915 | Version 3.3 | Yes | 1.43% |
| CVE-2025-41450 | Version 4.2 | Yes | 0.51% |
| CVE-2026-129713 | 5.5.x, no date | No | 0.98% |
The new flaw affects version 5.4.0 and earlier, and CISA scores it 9.8 (CVSS v3.1).
Jony Schats and Stan Plasmeijer of HackDefense, Synacktiv, and Max van der Horst of the Dutch Institute for Vulnerability Disclosure found the 2023 flaws. Carlo Meijer of Midnight Blue reported the new one.
Danfoss AK-SM 800A Flaws: Indicators of Compromise
CISA’s list names no attacker and no victim. No IP addresses, domains, or file hashes have been published for these flaws.